• 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 20
11 22 33 44 55 66 77 88 99 1010 1111 1212 1313 1414 1515 1616 1717 1818 1919 2020 2120
index_04
products
 

MAGNETIC, FLOAT OPERADED, GUIDED LEVEL SWITCH— "GHTP", "GHTJ"
WITH CONTROL UNIT— UMDG

 
It is an Established and Reliable Technique in Industry for single/ multiple liquid level sensing and control in open on pressurized vessels. It offer trouble free service in conductive / nonconductive liquids under widely varying Temperature, Pressures liquid viscosity and corrosive condition. Beside, it provides high repeatability and effect of shocks/ vibration are minimal

FEATURES:

  • Hermetically sealed glass encapsulated reed switch
  • Option of remote or integral control unit
  • Option of remote counter & totalizer for volume calculation
  • Option of intrinsically safe switch

CONSTRUCTION & OPERATION:

Simple & study construction, consisting of a float and guide tube, made of nonmagnetic material to achieve undisturbed magnetic flux.

The float has a magnetic system within it and moves freely along the guide tube, which contains glass encapsulated hermetically sealed reed switches, located at preset position. Float follows liquid level and magnetically actuates reed switch at preset position to give a change over contact. Single / multiple switching is effected through single or multiple float as required by application. Model GHTP is fitted with cast Al. enclosure to weather proof or Ex-proof to suit outdoor installations.


MAGNETIC, FLOAT OPERADED, GUIDED LEVEL SWITCH
Model GHTP is fitted with nylon plug in connector or epoxy potted to suit indoor installation only. Both models are available with "MICROSET Zener Barrier" for intrinsic safety. Low power, potential free contacts of reed switch can be directly connected PLC, DCS, or SCADA. Using along switch with MSSet Controller enhances its contact rating. Its relay contacts (5A, 230VAC) can be used to drive higher electric load.
 
INSTALLATION & WIRING:

Mounted internally or externally through a chamber as shown in Installation Drawing. External mounting is adopted to overcome limited space within the tank where mechanical devices like stirrers operate or where isolation tank is required for regular servicing. For installation without float removal, ensure 'Nozzle and Cage pipe' nominal bore is greater than float diameter.
 
request
 
Termination, Wiring & Installation:
 
MAGNETIC, FLOAT OPERADED, GUIDED LEVEL SWITCH
MAGNETIC, FLOAT OPERADED, GUIDED LEVEL SWITCH
 
Specification:
 

Installation

Outdoor Indoor
Mounting Top Top
Terminal Enclosure Cast Al., 1P66 Or Ex-p IIB or I IC Nylon, plug in Connector/Epoxy potted x,
flying extension leads (PVC-300)

11,Cable Glands

Polyimide x PG 9/11 or 1/2" NPT

Nylon, 6 to 10mm / NA I

Guide tube MOC

SS 316 / PP

SS 316

No. OF Float

Single/Multiple (Max.4)

Single (Max. 3)

Float MOC x Size

SS316x25, 28,41,60,75 &
90mm OR PPx50mm,
Nitrophyl x 17.5mm

SS316x 25, 28, 41mm PU
(Solid) x25mm,
Nitrophyl x17.5mm

Process Connections

Flanged, Screwed or
Triclover female
(Sanitary application)

Flanged, Screwed or
Triclover female
(Sanitary application)

Preset levels

1 to 4 (factory set)

a) Three (N/O switch), b) One
(C/0 switch)

Switch type

Glass encapsulated
hermetically sealed reed
contact
Glass encapsulated
hermetically sealed reed
contact

Switching Capacity

40VA (N/O) Or 60VA(1C/O)
Or120VA (N/O) Or
5VA(1C/O)
40VA (N/O) Or 60VA(1C/O)
Or120VA (N/O) Or
5VA(1C/O)

Differential

Fixed (10 ./- 5mm)

Fixed (3 to 5mm)

Accuracy / Repeatability

41- 2mrn & linm

+/-2mm & lmm

Load

Resistive Or Inductive

Resistive Or Inductive

Insulation

100M ohms at 500VDC

100M ohms at 500VDC

Max Temperature 150 deg. (Metallic) / 70deg. (PP) 100deg. (metallic) /70 deg. (PP)
Max Test Pressure 10 kg/cm2 (Metallic)/
3kg/cm2 (PP) 25kg/cm2
(Optional)
10kg/cm2 (Metallic)/ 2kg/cm2 (PP)
Special features Intrinsically safe to Ex ib Gr
LIB T6 (with Zener Barrier 24VDC/110mA)
Intrinsically safe to Ex ib Gr LIB T6 (with Zener Barrier 24VDC/110mA)
CE Certification Available with WP enclosure Available with plug in connector
 
FLOAT SELECTION TABLE FOR GHTP, GHTJ
 

Float SIZE
0DxLmm

MOC

NOMINA
L BORE
(NB)

TYPE

MIN
LIQUID
SP GR

TEST
PRESS
Kg/cm2

Max
TEMP

PRESET LEVELS

Max GTL MTR


40VA
IVO

60VA
1C/0


5VA
1C/0

120VA
N/O

17.5x26

Nitrophyl

15NB

A

≥ 0.8

1

70°C

3

-

1

-

1

25x25

PU (Solid)

25NB

B

≥ 0.8

1

70°C

3

-

1

-

1

25x25

55316

25NB

J

≥ 0.8

8

150°C

3

-

1

-

1

28x28

SS 316

32NB

C

≥0.8

10

150°C

3

-

1

-

1

41x38/52

SS316

40NB

D

≥1/0.65

10

150°C

4

4

4

4

3

50x60

PP

50NB

E

≥ 0.8

3

70°C

4

4

4

4

3

52x62

SS316

50NB

K

≥ 0.8

15

150°C

4

4

4

4

3

60x130

SS316

65NB

F

≥ 0.8

15

150°C

4

4

4

4

3

75x80

SS316

80NB

G

≥ 0.6

15

150°C

4

4

4

4

3

Non Std

 

 

0

               
 
   
 
pH Sensors   I   PH Electrode   I   Industrial Dip   I   Industrial pH Sensors   I   Sterilizable pH Sensors   I   Online PH Indicators / Controllers / Transmitters   I   pH Meters   I   
PH Bench Meter With 0.001 Resolution and Stability Indicator   I   Slim pH Meters   I   
Conductivity Sensor   
I   Conductivity Sensors   I   Conductivity Sensor - Industrial Pipeline   I   Conductivity Sensor - Industrial Dip   I   Sanitary Conductivity Sensor   I   Conductivity Indicating Controller Cum Transmitter   I   Conductivity Meter   I   Multi-ranging Conductivity, TDS, NaCl, Temperature Meter   I   Multi - Ranging Conductivity Meter   I   Dissolved Oxygen Sensors   IGalvanic-Maintenance Free DO2 Electrode  I   Polarographic DO2 Electrode   I   MSSet DO Sensor   I   DO ( Dissolved Oxygen ) Meter   I   Dissolved Oxygen Meters   I   Table Top Dissolved Oxygen Meters   I   Portable Dissolved Oxygen Meters   I   Ultrasonic Level Transmitters   I   Electromagnetic Flow Meters   I   pH Transmitters   I   On-line Panel Mounted PH Indicator cum Transmitter   I   Online pH Transmitters   I   Oxidation Reduction Potential   I   Oxidation Reduction Potential Sensor (I) – ( ORP Sensors )   I   Oxidation Reduction Potential Sensor – ( ORP Sensors )   I   Online Oxidation Reduction Potential Indicator, Controller and Transmitter   I  Oxidation Reduction Potential Transmitters - ( ORP Transmitters )   I   Ozone Amperometric Sensors   I   Dissolved Chlorine Sensors   I  TDS Indicating Controller   I   Magnetic Flowmeter   I   Dissolved Chlorine Dioxide Sensors   I   Dissolved Oxygen Transmitter - ( DO Transmitter )   I   Conductivity Transmitters MS-CT-211T  II  Temperature And Air Velociy Transmitters DUW 221  II   Clamp On Ultrasonic Flow Meters  II   Process Conductivity / TDS Controllers & Transmitter  II   MS Controller Bsed Conductivity Indicators / Controller  II   Electromagnetic Flow Meters MS FL 0117  II   High Precision Air / Gas Velocity Transmitter  II   Magnetic Float Operaded, Guided Level Switch  II   MS Controller Based Conductivity / TDS  II   MS controller Based PH Indicator / Controller  II   MS Controller Based ORP Indicatorsc / Controller  II   Digital pH Indicator CUM Transmitter  II   MS Controller Based pH Meters MS pH 644  II   Digital Bench Top pH Meters  II   Digital Bench Top TDS / Conductivity Meter  II   MS Controller Based TDS Indicators / Contorller  II   UPVc Electromagnetic Flow Meters MS FL 0117  I   Home   I   About Us   I   Contact Us   I
Enquiry   I   Sitemap